Guest mode. You can read posts without signing up. Comments, ratings, job contacts and your own posts open after you sign up and accept the rules. What is Kommit →

Редакция КоммитРедакция портала
commit f5d30c2 · 19 days ago

ACS, part 2: budget option — autonomous controller for one or two doors

🌐 Machine-translated from Russian. Show original

In this part:

Who is it suitable for#

Small office, store, warehouse, server room: one or two doors, up to several dozen employees, no or minimal passage log required.

Set#

  • A standalone controller with a reader (often in the same case as the keyboard) or separate controller and reader.
  • Lock: electromagnetic for glass and light doors, electromechanical latch for regular doors.
  • Exit button from inside.
  • 12V power supply with battery — lock and controller operate during power outages.
  • Closer — without it, the door will remain slightly open and the lock won't work.
  • Cards or key fobs (preferably 13.56 MHz, see part 1.

Many manufacturers produce such kits — from budget brands to ZKTeco, Hikvision, and Dahua.

Wiring diagram#

[Считыватель/клавиатура] ── контроллер ── реле ──> [Замок]
                               │
                 [Кнопка выхода]  [Датчик двери]
                               │
                 [Блок питания 12 В + АКБ]
  • The lock is powered through a controller relay and must have a protective diode (often included) — otherwise, voltage surges when the electromagnet is disconnected will damage the controller.
  • The output button connects to the controller input, not directly into the lock circuit — this is how the controller locks the output.
  • On evacuation routes, there is an emergency release button that cuts the lock power directly.

Programming#

Typical order for standalone controllers (specific codes are in the model manual):

  1. Enter programming mode with master code or master card and change the factory master code.
  2. Add cards: bring them in turn or enter numbers from the keyboard.
  3. Set the lock opening time (usually 3–5 seconds).
  4. Check the entry, button exit, and operation when the power is disconnected (on the battery).

Card accounting#

Even in an offline system, keep a table: card number → employee → date of issue. When dismissed, the card must be removed from the controller, not just taken away: the employee could have made a copy.

Limitations#

  • No remote control: you can only add or remove a card at the door.
  • The pass log is missing or hard to obtain.
  • Scaling to 3+ doors turns into bypassing all controllers with each change.

When these restrictions start to get in the way, it's time to switch to a network system.

Comments 00 участников · 1 гость🔒 Rate and discuss after signing up

Comments · 0

No comments yet.Sign in to comment, rate and see all comments.