DCS, Part 4: Enterprise Level — Branches, Integrations, Fire Safety, and Fault Tolerance
🌐 Machine-translated from Russian. Show original
In this part:
What distinguishes the corporate level#
- Many facilities — offices, warehouses, branches in different cities in one system.
- Thousands of users and a complex role-playing model.
- Integrations: HR system, Active Directory, video surveillance, security and fire alarms, pass bureau.
- Fault tolerance: the doors operate even when the central server is unavailable.
- Requirements of security services, auditors, and regulators.
Solutions of this level are available from industry DCD manufacturers (Sigur, PERCo, Parsec, Bolid are widespread in the region), as well as from international platforms (HID, Honeywell, Gallagher, Lenel, Genetec, etc.), and video production platforms (HikCentral, DSS).
Architecture#
- A central server (or cluster) with a database and backup.
- Controllers store the database and decisions locally: if communication with the server is lost, the pass continues to run, events accumulate and are transmitted later.
- Branches — via secure channels (VPN), and if necessary — local servers.
- Workplaces: pass office, security post, HR department, administrator.
Integrations#
| What | What gives |
|---|---|
| HR system / 1C:ZUP | employee hired — their rights are issued automatically; dismissed — the pass is blocked on the same day |
| Active Directory | unified accounts and groups, division synchronization, |
| Video surveillance | a frame or video for each passing event, checking whether it passed on its own map |
| Security alarm | setting up security zones at the last exit of the |
| Fire alarm | automatic unlocking of evacuation routes |
| Recording of working hours | pass data → timesheet, see SURV series |
Fire safety#
This is not an option, but a mandatory requirement:
- When a fire alarm is sounded, locks on evacuation routes are unlocked, turnstiles are opened.
- Unlocking must operate hardware— based on a signal from the fire alarm device, not just through software.
- On evacuation routes — fail-safe locks (part 1 ) and emergency unlock buttons.
- Requirements for such solutions are determined by fire safety standards — coordinate the project with the fire safety system designer.
Visitors and pass bureaus#
- A request for a pass from an employee → approval → a temporary card or QR code with time and zone restrictions.
- Scanning the visitor's document is only up to the extent necessary for the pass, taking into account personal data requirements.
- Return of temporary cards at the exit (card collector on the turnstile).
Security of the ACS itself#
- Secure cards or mobile keys, OSDP Secure Channel between readers and controllers.
- Rights differentiation in software: the post operator sees events but does not change access rights.
- Administrator activity log, server reservations, and regular backups.
- Annual audit: role-playing rights, unused cards, "perpetual" guest passes.
Next comes the editing.